Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/18/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 02/13/2004 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ PLEASE INSTALL C.O. AS PER PLAN. |
| 12/16/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ HANGERS REQUIRED AT EACH CHANGE OF DIRECTION OR ELEVATION, AND THEN SPACED PER TABLE 3-1, 94 UPC. FLOOR SINK AT DARK ROOM REQUIRED BY PLAN. CONDENSATE WASTE AS WELL AS RPPBP DRAIN TO DUMP INTO APPROVED INDIRECT WASTE RECEPTOR. PLAN CALLS FOR 3/4" HOSE BIB. CALL WHEN ADDITIONAL HANGERS WELDED. OK TO COVER WALLS. |