Permit: T03CM03807

Parcel: 10819008G


Addresses:

4558 N 1ST AV #110

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/18/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
02/13/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ PLEASE INSTALL C.O. AS PER PLAN.
12/16/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ HANGERS REQUIRED AT EACH CHANGE OF DIRECTION OR ELEVATION, AND THEN SPACED PER TABLE 3-1, 94 UPC. FLOOR SINK AT DARK ROOM REQUIRED BY PLAN. CONDENSATE WASTE AS WELL AS RPPBP DRAIN TO DUMP INTO APPROVED INDIRECT WASTE RECEPTOR. PLAN CALLS FOR 3/4" HOSE BIB. CALL WHEN ADDITIONAL HANGERS WELDED. OK TO COVER WALLS.