Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/09/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET 2) USE PURPLE PRIMER PRIOR TO GLUING PVC FITTINGS 3) PROVIDE AN AIR BALANCE REPORT 4) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND WITH AN ELBOW AND NIPPLE 5) PROVIDE A GFI SERVICE RECEPTACLE AT CONDENSOR 6) A/C EQUIPMENT TO BE 5 TON AS PER PLANS OR PROVIDE LETTER FROM ARCHITECT OR ENGINEER |