Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/09/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) MAINTAIN WORKING SPACE 110.26 PANEL AND A/C 2) FINISH PANEL DIRECTORY PER 408.4 3) LABEL TIME CLOCK 4) BOXES NEEDED AT BATH BARS 5) EXIST SIGNS NEED EM LIGHTS PER PLANS AND PER 700.12 (F) 6) MISSING GFCI BY A/C |
|
| 11/22/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |