Permit: T03CM03775

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03CM03775

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2003 PLUMBING - FINAL Approved
10/16/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) SUPPORT 1/2" COPPER RISERS AT PRESSURE VACUUM BREAKER 2) TRAPS AND TRAP ARMS TO BE THE SAME SIZE 3) ONLY ONE SLIP NUT ALLOWED ON THE OUTLET SIDE OF THE TRAP 4) SUPPORT TRAP PRIMER DRAIN
10/13/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/1) ATMOSPHERIC VACUUM BREAKER MAY NOT HAVE A VALVE DOWNSTREAM, MAY NOT BE UNDER CONSTANT PRESSURE - MUST BE A TESTABLE DEVICE. 2) 4"X2" N/H BELL REDUCER IS NOT AN APPROVED INDIRECT WASTE RECEPTACLE. 3) INSTALLATION MANUAL SHOWS DIRECT CONNECTION TO SANITARY SEWER. 4) MAY NOT BE A COMPLETE LIST CHECK ALL WORK.
10/10/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ ABOVE CEILING OK TO COVER.
10/09/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
10/06/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ OVERHEAD PIPING NOT INSTALLED PER PLAN. FINAL NOT READY.
10/02/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*