Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM03775
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2003 | PLUMBING - FINAL | Approved | ||
10/16/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) SUPPORT 1/2" COPPER RISERS AT PRESSURE VACUUM BREAKER 2) TRAPS AND TRAP ARMS TO BE THE SAME SIZE 3) ONLY ONE SLIP NUT ALLOWED ON THE OUTLET SIDE OF THE TRAP 4) SUPPORT TRAP PRIMER DRAIN | |
10/13/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/1) ATMOSPHERIC VACUUM BREAKER MAY NOT HAVE A VALVE DOWNSTREAM, MAY NOT BE UNDER CONSTANT PRESSURE - MUST BE A TESTABLE DEVICE. 2) 4"X2" N/H BELL REDUCER IS NOT AN APPROVED INDIRECT WASTE RECEPTACLE. 3) INSTALLATION MANUAL SHOWS DIRECT CONNECTION TO SANITARY SEWER. 4) MAY NOT BE A COMPLETE LIST CHECK ALL WORK. | |
10/10/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ ABOVE CEILING OK TO COVER. | |
10/09/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
10/06/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ OVERHEAD PIPING NOT INSTALLED PER PLAN. FINAL NOT READY. | |
10/02/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |