Permit: T03CM03775

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM03775

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/02/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
10/01/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*
09/30/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*/ 1) 2 X 2 FLOUR FIXTURES MUST BE CLIPPED OR SCREWED TO MAIN RUNNERS OF 'T' BAR CEILING 2) REMOVE ANY UNSUED FIXTURES FROM CEILING 3) WIRE TERMINATION ON ONE FIXTURE IS INCOMPLETE 4) SUPPORT 'J' BOXES WITH THEIR OWN DROP WIRE OR THREADED ROD. CORRECT AND RECALL
09/22/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ PARTIAL OK, SOFFIT LIGHTS.