Permit: T03CM03769

Parcel: 12104107A


Addresses:

5702 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/31/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000* 1) OK FINAL
12/30/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) MAINTENCE RECEPTACLE SAME LEVEL 2) PROVIDE NUMBER OF EM FLOODS AS PER PLANS
12/23/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) BREAKER TO BE POSITIONED IN PANEL TO NOTCHED POSITIONS. 2) A GROUNDING ELECTRODE SYSTEM IS NEEDED. 3) LABEL DISCONNECTS TO A/C'S. 4) SUPPORT CONDUITS 3' AS PER CODE. 5) MAITENANCE RECEPTACLES NEEDED.
12/22/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
12/18/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) BONDING DEVICE NEEDED BOTH SIDES OF SERVICE NIPPLE 250.94 2) INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURER LABEL 3) CUSTOMER ASKED INSPECTOR TO LEAVE JOB
12/15/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) SEE WRITE-UP FOR 5704 E. GRANT