Permit: T03CM03769

Parcel: 12104107A


Addresses:

5702 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/06/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
10/03/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK 1ST FLOOR 2) FINISH #2 OF PREVIOUS WRITE UP- 2ND FLOOR
09/19/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) PROTECT CABLES PASSING THROUGH STUDS 2) STAPLE CABLE WITH IN 12" OF BOX AND CANS 3) WE HAVE CONDUCTOR OVERFILL AT BOXES 4) PROTECT CABLE FROM SHARP EDGES ENTERING FLEX CONDUIT 5) WHERE IS PANEL FEEDER UPSTAIRS PANEL ? 6) PANEL ON PLANS TO BE 200A WE HAVE 125 AMP 7) HAVE APPROVED STAMPED PLANS ON SITE