Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/06/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 10/03/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK 1ST FLOOR 2) FINISH #2 OF PREVIOUS WRITE UP- 2ND FLOOR |
| 09/19/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) PROTECT CABLES PASSING THROUGH STUDS 2) STAPLE CABLE WITH IN 12" OF BOX AND CANS 3) WE HAVE CONDUCTOR OVERFILL AT BOXES 4) PROTECT CABLE FROM SHARP EDGES ENTERING FLEX CONDUIT 5) WHERE IS PANEL FEEDER UPSTAIRS PANEL ? 6) PANEL ON PLANS TO BE 200A WE HAVE 125 AMP 7) HAVE APPROVED STAMPED PLANS ON SITE |