Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/11/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ K.O. SEALS - DISCONNECT TO BE REMOVED. |
| 02/10/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FILL UNUSED OPENINGS IN BOXES 2) MAINTAIN WORKING CLEARANCES IN FRONT OF DISCONNECT |
| 12/23/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 370.20-METAL NOT APPROVED 2) WHERE IS DISCONNECT IN ROOM NUMBER DARKROOM 3) PLANS CALL FOR #1 TO FEED SUB PANEL-ALSO LUG 600.1 4) WILL NEED TO SEE EQUIPMENT CONNECTIONS |
| 12/22/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ ELECTRICAL CONTRACTORS SCOPE OF WORK IS COMPLETED. TEMP C OF O SUBJECT TO OTHER INSPECTIONS. NEED TO SEE EQUIPMENT CONNECTORS. |