Permit: T03CM03764

Parcel: 12513002B


Addresses:

3244 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
12/22/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
12/19/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) FINISH ACCESS HOLES 2) SUPPORT M/C CABLE AS PER CODE 3) FILL UNUSED OPENINGS 4) FINISH DATA SUPPORTS
12/15/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*/ 1) NO WORK PROGRESS-JUNCTION BOXES NOT ACCESSIBLE 2) WE NOW HAVE DATA CABLE LAYING ON GRID
11/24/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*
11/19/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*/ NEEDS TO TALK TO RICK H. PRIOR TO INSP.
11/13/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*/ 1) JUNCTION BOXES TO BE ACCESSIBLE 2) EXHAUST FANS ABOVE HARD CEILING NOT INSTALLED 3) PLEASE UNCOVER CEILING FOR INSPECTION
11/06/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*/ 1) CHECK CONDUCTOR FILL FOR BOXES 2) FINISH ITEMS 1,2, 3 FROM PREVIOUS INSPECTION
10/27/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) NO MORE THAN 360 DEGREE IN A RUN OF CONDUIT 2) SUPPORT WIRES NEEDED ON ALL BOXES IN CEILING 3) PLEASE ATTACH FIXTURE TO GRID 4) OK WALLS
10/22/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*/ NOTES: 1) MC CABLE TO BE SUPPORTED WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS. 2) MUST HAVE AT LEAST 1-1/4" SPACE CLEARANCE FOR SCREWS WHERE MC RUN INSIDE STUD. 3) BLACK TIE WIRE NOT APPROVED FOR FIXTURE SIZEMIC TIES, USE #9 CEILING WIRE. 4) EMT CONDUIT TO BE SUPPORTED WITHIN 3' EACH TERMINATION AND AT 10' INTERVALS PER NEC. 5) PLANS/PERMIT MUST BE ON SITE.