Permit: T03CM03753

Parcel: 13610023L


Addresses:

2601 S HOUGHTON RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM03753

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*OK FOR FINAL
01/05/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* CIRCUIT BREAKERS FOR A/C UNITS NOT ?? CORRECTLY. SEE UNIT DATA PLATE FOR PROPER SIZE. RTU-4 HEAT STRIP NOT IDENTIFIED. NEED FANS RUNNING TO TEST DUCT SMOKE DETECTORS.
11/09/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/OK TEMP POWER FOR TESTING
10/14/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/1)PROVIDE ECONOMIZERS AS PER PLANS 2)PERMANEATLY IDENTIFY A/C UNITS 3)MARK UNIT DATA PLATES W/PROPER HEAT STRIP INSTALLED 4)NEED TO TEST DUCT SMOKE DETECTORS.