Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/01/2005 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 05/25/2005 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* |
| 07/08/2004 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) WASTE AND VENT AIR TEST 6 PSI THRU ROOF OK 2) NEED TO SEE ROOF FLASHINGS 3) CLOSET FLANGES OK |
| 07/07/2004 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) WATER PIPING AIR TEST 60 PSI OK 2) NEED TO SEE AIR OR WATER TEST ON WASTE AND VENT |
| 06/30/2004 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ EXTERIOR WALLS OF SALES FLOOR ONLY. PIPING SHALL WITH STAND AIR PRESSURE TEST. CHECK YOUR FIXTURE UNIT COUNT ON YOUR VENT SIZING IN RESTROOM AREA, POSSIBLY APPROVED IN ERROR ON PLAN, INSTALL PER CODE. |
| 06/17/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :*/ TRAP PRIMERS OK. WRAP ALL PIPES PENETRATIONS THRU CONCRETE FLOOR. |
| 06/02/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :* |