Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/03/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 02/24/2004 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) ELECTRIC OUTLETS REQUIRED WITHIN 6 FEET OF DOORS BETWEEN PATIO DOORS AT FIXED PANELS 2) PROVIDE ROTATION CONTROL BLOCKS ON TJI'S WEST WALL PER TJI INSTRUCTIONS 3) W/H 'B' VENT MISSING 4) FIRE BLOCK KITCHEN DROP CEILING 5) REMOVE OUTLET FROM UNDER COUNTER 6) SHOWER MUST HAVE TEMP/PRESSURE BALANCED ANTI SCALD VALVES 7) DWV WATER TEST OK TO DRAIN |
| 02/23/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLUMBER STILL WORKING |