Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 08/22/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 08/21/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/ 1) REINFORCING STEEL REQUIRES 1 1/2" CLEARANCE TO ALL PLUMBING STACKS AND BLOCK OUTS 2) TOP AND BOTTOM RACKS OF REBAR REQUIRE SEPERATION PER DETAILS A, B, C, D AND E PAGE A-1 3) REBAR REQUIRES 2" CLEARANCE TO F.F. SEE DETAILS |