Permit: T03CM03722

Parcel: 10409001C


Addresses:

4365 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03CM03722

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/13/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ 1) CORRECTIONS MADE OK. PLBG FINAL OK. 2) OK FOR C OF O PENDING ANY OTHER INSP.
05/12/2004 PLUMBING - FINAL Not ready for Inspection 1) CALLED NO. - LEFT MESSAGE. 2) UNABLE TO LOCATE PLAN OR PERMIT. 3) HOW DOES PLAN SHOW R.O. WTR DRAIN TERMINATION? MUST BE INDIRECT.
04/28/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) NOT READY FOR INSPECTION
04/06/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ HAVE PLBR COMPLETE HIS PUNCH LIST BEFORE RECALLING FINAL INSPECTION. HAVE BACKFLOW CERTIFICATIONS AND PROVIDE LISTING FOR R.O. UNIT. DRAIN TO BE INDIRECTLY WASTED - MAY NOT CONNECT TO TAILPEICE. WHERE IS VACUUM BREAKER ON HOSE FOR SINK? FINISH ALL INSTALLATION.
03/25/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) TWO SINKS NOT SET - NO CABINETS. 2) CENTERLINE TO SIDE WALL ON URINAL MIN. 12", 15" REQUIRED FOR ADA. 3) 15" REQUIRED FOR CENTER TO SIDEWALL ON WTR CLOSETS. 4) NO PHARMACY OR PHOTO EQUIPMENT SET. 5) CUT DOWN OUTSIDE C.O. 6) TEMP C OF O SUBJECT TO OTHER INSPECTORS AND STEVE LONG.
03/10/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ OK FOR TEMP POWER S.T.O.I.