Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM03722
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
02/12/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ PVC RUNS FOR LIGHTING AND SIGNS. | |
02/10/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) ALL EXTERIOR CANOPIES. 2) GROUND RODS AT PRKG LITE BASES. | |
01/29/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ SECONDARY POWER CONDUIT [3X4"] PVC, BATHROOMS AND WAREHOUSE. | |
01/16/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) 10 POLE BASES OK TO POUR. 2) EAST AND NORTH SIDE TRENCHING TO POLES OK TO COVER. 3) REMAINDER OF ALL INTERIOR/OUTSIDE WALLS OK TO COVER. | |
01/14/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) CONDUIT AND BOXES AT FRONT OF BLDG AND WALLS NORTH AND SOUTH TO THE DEMISING WALL AT REAR. REAR WAREHOUDE SECTION IS INCOMPLETE. | |
12/31/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ SITE LIGHTING AND SIGN POWER UNDERGROUND PVC. | |
12/15/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ UNDERSLAB CONDUIT. | |
12/10/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) PVC RUNS FOR TELEPHONE AND DATA CABLES, RUN UNDER SLAB |