Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM03702
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
| 09/16/2003 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) SECURE HOLDOWNS AND AB'S 2) OVER BORED STRUDS, GARAGE AND KITCHEN 3) ADD 1-AB AT GARAGE SHEAR 4) COMPLETE PORCH LEDGER DETAIL 5) SEAL VAPOR BARRIER (MOISTURE) 6) GABLE BRACING PER DETAIL 7) NAIL PLATE 220 V 8) SHIM HEADER AT GARAGE PLATFORM 9) NAIL PLATE ELECTRIC CONDUCTORS WITH 1 1/4" OF STUD EDGE 10) NAIL PLATE WATER AT EXTERIOR HOSE BIB AND SUPPORT, MB WC VENT, MB BATHTUB VENT, WATER AT HALL BATH 11) SEAL TEARS IN DUCTS | |
| 09/15/2003 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) OVER BORED STUDS 2) SHIM HEADER AT PLATFORM 3) FIRE STOP PLATFORM 4) SHEAR TRANSFER PER DETAIL AT GARAGE WALL 5) GABLE BRACE PER DETAIL 6) SEAL VAPOR BARRIER 7) NO TESTS | |
| 09/14/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* | |
| 09/10/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) CANCELLED ON SITE |