Permit: T03CM03698

Parcel: 108163280

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/26/2003 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
09/18/2003 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) 3 POINT BEARING TRUSSES IMMEDIATELY INSIDE FRONT DOOR HAVE BEARING POINT AT WRONG LOCATION-PROVIDE ENGINEERING AND FIELD REPAIR 2) CLIP TRUSSES AT 3RD BEARING POINT 3) PROVIDE TRUSS CALC'S 4) #5 SHEAR REQUIRES A.B.'S AT 24" ON CENTER 5) OK TO DRY IN ROOF PENDING ENGINEERING APPROVAL ON TRUSS REPAIR
09/16/2003 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED ON SITE BY SUPER