Inspection Status: Denied
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T03CM03697
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection 0999*/ 1) EXPOSE FOOTING ON STRUCTURE TO PROVIDE DEPTH AND WIDTH OF FOUNDATION 2) STUCCO ONE COAT SYSTEM REQUIRES WEEP SCREED AT BOTTOM 3) EXPOSE 3' X 3' SECTION OF STUCCO LATH 4) EXPOSE HD5A HOLDOWNS 5) BRACED WALL PANEL NOT INSTALLED 6) OVER SPANNED 2 X 6 RAFTERS MUST BE SPACED AT 12" ON CENTER 7) BEAM AT GARAGE MID POINT NOT PER PLAN 8) HEADERS MUST BEAR ON TRIMMERS 9) PROVIDE PROOF OF REINFORCING STEEL 1) 8/A3 NOT COMPLIED WITH 11) EXPOSE ALL HEADER/ POST AND BEAM CONNECTIONS 12) EXPOSE ALL ANCHOR BOLTS 13) UNTREATED WOOD CANNOT BE IN CONTACT WITH CONCRETE 14) STRUCTURE NOT BUILT PER PLAN 15) STOPPED INSPECTION |