Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM03697

Parcel: 118033630


Addresses:

2334 S FORREST AV


Inspection Status: Denied

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T03CM03697

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Denied

Date Description Inspector Results Comments
03/01/2004 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection 0999*/ 1) EXPOSE FOOTING ON STRUCTURE TO PROVIDE DEPTH AND WIDTH OF FOUNDATION 2) STUCCO ONE COAT SYSTEM REQUIRES WEEP SCREED AT BOTTOM 3) EXPOSE 3' X 3' SECTION OF STUCCO LATH 4) EXPOSE HD5A HOLDOWNS 5) BRACED WALL PANEL NOT INSTALLED 6) OVER SPANNED 2 X 6 RAFTERS MUST BE SPACED AT 12" ON CENTER 7) BEAM AT GARAGE MID POINT NOT PER PLAN 8) HEADERS MUST BEAR ON TRIMMERS 9) PROVIDE PROOF OF REINFORCING STEEL 1) 8/A3 NOT COMPLIED WITH 11) EXPOSE ALL HEADER/ POST AND BEAM CONNECTIONS 12) EXPOSE ALL ANCHOR BOLTS 13) UNTREATED WOOD CANNOT BE IN CONTACT WITH CONCRETE 14) STRUCTURE NOT BUILT PER PLAN 15) STOPPED INSPECTION