Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM03687

Parcel: 13355231A

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T03CM03687

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
06/09/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
04/29/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
04/27/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*/ 10 PSI PRESSURE TEST SHALL BE ON SYSTEM AT TIME OF INSP. 2) PROVIDE RUST PROOF SCREWS FOR STRAPS SECURING PIPING ON ROOF. 3) SEAL PIPE PENETRATION THRU EXTERIOR WALL. 4) PROVIDE CITY APPROVED GAS PLAN FOR PETER PIPER SECTION. 15 PSI PRESSURE TES ON EAST 2" SERVICE FOR PIER 1 TO VH AND 3 ROOF TOP UNITS OK. SEE NOTES FROM PREVIOUS INSP.
03/01/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection 0000*