Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 06/09/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Approved |
IVRS - Inspection :* |
| 03/15/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Partial Approval |
IVRS - Inspection 0000*/ LINE PRESSURE ON TWO 1½" COPPER LINES FROM METER THRU 1½" BACKFLOW PROTECTION DEVICES TIEING INTO 2" BLDG SERVICES OK. PENDING CITY APPROVED DRAWING SHOWING 1½" PIPING AND BACKFLOW DEVICES IS OK. |
| 03/11/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) EXPOSE YARD WTR PIPING. 2) NO INTERMINGLING OF GALV. PIPING ON COPPER H2O SYSTEM. MUST USE DIELECTRIC FITTINGS. |