Permit: T03CM03677

Parcel: 129140100


Addresses:

707 E 37TH ST


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T03CM03677

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
08/16/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/29/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NO PRIOR INSPECTION REPORTS ON SITE 2) NO SPECIAL INSPECTION REPORT FOR EPOXY BOLTS 3) PROVIDE HOLDOWN/POST ON BASE GARAGE GLU LAM BEAM POST AT CARPORT 4) DBL TOP PLATES CUT 4 LOCATIONS. COMPLY WITH 4/10 OR PRVOIDE ENGINEERS REPAIR
07/21/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) 2/10 KNEE BRACES REQUIRED AT 32" ON CENTER 2) ITEM 2 OF 6/25/04 NOT COMPLIED WITH 3) PROVIDE EPOXY BOLT SPECIAL INSPECTION REPORT 4) PROVIDE LADDER ACCESS FOR ROOF INSPECTION 5) STOPPED INSPECTION, TOO MANY ITEMS