Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/12/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REAR PORCH BEAMS TO BE 6 X 8 PER PLAN 2) INSTALL GABLE END VENTS 3) PLANS CALLS FOR 1" GAS LINE TO RANGE, 3/4" TO H20 HEATER 4) GROUND ALL METAL ELECTRIC BOXES 5) INSTALL PORCH ELECTRIC BOXES 6) NO TEST DWV 7) INSTALL BANG PLATES PLUMBING AND ELECTRIC THROUGHOUT 8) DRYER EXHAUST VENT TO BE 4" DIAMETER PER PLAN 9) PROVIDE COMBUSTION AND RELIEF MECHANICAL VENTS H20 HEATER MINIMUM 100 SQUARE INCH TOP AND BOTTOM 10) COMPLETE ALL TO PALN/CODE AND RECALL 11) STOPPED INSPECTION |