Permit: T03CM03657


Addresses:

222 S FREEWAY M1

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/22/2006 BUILDING - FINAL Approved
07/24/2006 BUILDING - FINAL Partial Approval IVRS - Inspection :*
YOU NEED TO GET APPROVED AS BUILT
OK TO CONTINUE TCO
01/20/2006 BUILDING - FINAL Partial Approval OK FOR TEMP C OF O FOR GEM SHOW ONLY PER INS COPY
ITEMS 3 & 4 BELOW AND NOTICE ABOVE TO BE ADDRESSED AFTER GEM SHOW
01/17/2006 BUILDING - FINAL Partial Approval IVRS - Inspection :*
OK TCO FOR GEM SHOW
1. RAMPS REQUIRE HANDRAILS ON BOTH SIDES WHEN RISE IS GREATER THAN 6'
2. ACCESSIBLE ENTRANCE REQUIRES 18" SIDE CLEARANCE ON PULL SIDE AT DOOR (AT ACCESSIBLE RAMP)
3. GUARDS AT LANDINGS AND STAIRS TO BE 42" HIGH WITH HANDRAILS @ 34" PER NOTES PP3. PLEASE NOTE EXCEPTION CODE TO ALLOW HANDRAIL AS GUARD DOES NOT APPLY TO A OCCUPANCIES.
4. WOMEN'S RESTROOM DOES NOT HAVE REQUIRED 18" SIDE CLEARANCE AT PULL SIDE OF DOOR AND DOOR SWING OVERLAPS CLEAR FLOOR SPACE FOR LAV