Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/02/2005 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 11/24/2004 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* |
| 11/19/2004 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* |
| 06/30/2004 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :*/ 1) BONDING JUMPER TO BE SIZED PER 250-102 AND 250-66 2) HIGH LEG TO BE AS PER CODE FOR PHASE PLACEMENT AND EQUIPMENT LABELED AS SUCH 3) TIGHTEN TERMINATIONS 4) REJECTION PINS ARE NEEDED 5) GUTTER SCREWS STRIPPED OUT 6) PLEASE ID NEUTRAL CLOSER TO WEATHER HEAD 7) PLEASE REVISE PLANS TO REFLECT WORK INSTALLED AND HAVE STAMPED APPROVAL |
| 06/09/2004 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) SUPPORT MC CABLE WITHIN 12" OF BOX. 2) PLEASE REMOVE BARRIER PAPER FOR INSP. 3) FINISH CONDUITS TO PANEL. 4) PLEASE PROVIDE LETTER AUTHORIZING USE OF MC CABLE PLANS CALL FOR CONDUIT. 5) PLEASE VERIFY TYPE OF GRID CEILING. PVC CONDUIT NOT ALLOWED IN A PLENIUM RATED CEILING. |
| 04/12/2004 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |