Permit: T03CM03655

Parcel: 122010740


Addresses:

4125 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
02/02/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/24/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/19/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/30/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) BONDING JUMPER TO BE SIZED PER 250-102 AND 250-66 2) HIGH LEG TO BE AS PER CODE FOR PHASE PLACEMENT AND EQUIPMENT LABELED AS SUCH 3) TIGHTEN TERMINATIONS 4) REJECTION PINS ARE NEEDED 5) GUTTER SCREWS STRIPPED OUT 6) PLEASE ID NEUTRAL CLOSER TO WEATHER HEAD 7) PLEASE REVISE PLANS TO REFLECT WORK INSTALLED AND HAVE STAMPED APPROVAL
06/09/2004 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*/ 1) SUPPORT MC CABLE WITHIN 12" OF BOX. 2) PLEASE REMOVE BARRIER PAPER FOR INSP. 3) FINISH CONDUITS TO PANEL. 4) PLEASE PROVIDE LETTER AUTHORIZING USE OF MC CABLE PLANS CALL FOR CONDUIT. 5) PLEASE VERIFY TYPE OF GRID CEILING. PVC CONDUIT NOT ALLOWED IN A PLENIUM RATED CEILING.
04/12/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*