Permit: T03CM03650

Parcel: 123130070


Addresses:

856 E GRANT RD #02


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T03CM03650

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/04/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
08/28/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*
08/26/2003 BUILDING - FINAL Partial Approval IVRS - Inspection 0000*/ 1) LAUNDRY AND BATH VENT INCOMPLETE AND PAINT LATEX 2) INSTALL GROUND ROD AND CONDUCTOR SUB-PANEL 3) PLUG ELECTRIC PANEL KNOCKOUTS 4) GAS PIPING HOLDING PRESSURE INSIDE, CONNECT PIPING TO METER AND RETEST
07/30/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) LAUNDRY DRAIN NOT VENTED 2) ALL KITCHEN COUNTER OUTLETS MUST BE GFCI PROTECTED. GFCI OUTLET WIRED INCORRECTLY-HOT WHEN TRIPPED 3) ALL COUNTER SPACES GREATER THAN 12" REQUIRE GFCI OUTLET 4) BATHROOM LAV NOT VENTED 5) W/H "B" VENT REQUIRES 1" TO COMBUSTIBLES 6) PROVIDE 100 SQUARE HIGH AND LOW COMBUSTION AIR FOR WATER HEATER 7) W/H T & P MUST EXHAUST OUTSIDE 3/4 LINE EXHAUST DOWN 8) HOUSE REQUIRES 2 DEDICATED CIRCUIT BASE BOARD HEATERS 9) LABEL ALL CIRCUITS IN ELECTRIC PANEL FILL KOS 10) BEDROOM REQUIRES SMOKE DETECTOR 11) GAS LINE MUST BE 12" BELOW OR 6" ABOVE GRADE. PROVIDE 10 PSI MINIMUM GAS PRESSURE TEST