Permit: T03CM03648

Parcel: 12108001B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM03648

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK FINAL
09/17/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) COMPLETE INSPECTION DATE 9/16/03-APPROVED EXTENDER RINGS NEEDED FOR BOXES MORE THAN 1/4" 2) ATTACH FIXTURES TO GRID 410.16 3) PROVIDE LETTER FROM ELECTRICAL CONTRACTOR AS DISCUSSED 4) IF ITEMS ARE NOT CORRECTED A REFEE PER ADMINISTRATION CODES MAY BE ACCESSED
09/16/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) FINISH INSTALLATION OF ELECTRIC 2) IF BOXES MORE THAN 1/4" FROM BOX TO SURFACE AND APPROVED EXTENDER RING IS NEEDED 370.20 METAL NOT APPROVED 3) TIGHTEN LOOSE CONDUIT FITTINGS TO A/C 4) ATTACH FIXTURES TO GRID 410-16
09/15/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0950*/ HAVE REVISED PANEL SCHEDULE APPROVED BY PLAN REVIEW. WAS WATER HEATER ADDED? 2) ADD BLANK COVER OVER CIRCUIT BREAKER OPENING.
09/10/2003 ELECTRIC - FINAL Cancelled IVRS - Ri canceled