Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM03648
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) OK FINAL | |
09/17/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) COMPLETE INSPECTION DATE 9/16/03-APPROVED EXTENDER RINGS NEEDED FOR BOXES MORE THAN 1/4" 2) ATTACH FIXTURES TO GRID 410.16 3) PROVIDE LETTER FROM ELECTRICAL CONTRACTOR AS DISCUSSED 4) IF ITEMS ARE NOT CORRECTED A REFEE PER ADMINISTRATION CODES MAY BE ACCESSED | |
09/16/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) FINISH INSTALLATION OF ELECTRIC 2) IF BOXES MORE THAN 1/4" FROM BOX TO SURFACE AND APPROVED EXTENDER RING IS NEEDED 370.20 METAL NOT APPROVED 3) TIGHTEN LOOSE CONDUIT FITTINGS TO A/C 4) ATTACH FIXTURES TO GRID 410-16 | |
09/15/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0950*/ HAVE REVISED PANEL SCHEDULE APPROVED BY PLAN REVIEW. WAS WATER HEATER ADDED? 2) ADD BLANK COVER OVER CIRCUIT BREAKER OPENING. | |
09/10/2003 | ELECTRIC - FINAL | Cancelled | IVRS - Ri canceled |