Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/18/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 09/17/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) COMPLETE INSPECTION DATE 9/16/03-APPROVED EXTENDER RINGS NEEDED FOR BOXES MORE THAN 1/4" 2) ATTACH FIXTURES TO GRID 410.16 3) PROVIDE LETTER FROM ELECTRICAL CONTRACTOR AS DISCUSSED 4) IF ITEMS ARE NOT CORRECTED A REFEE PER ADMINISTRATION CODES MAY BE ACCESSED |
| 09/16/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) FINISH INSTALLATION OF ELECTRIC 2) IF BOXES MORE THAN 1/4" FROM BOX TO SURFACE AND APPROVED EXTENDER RING IS NEEDED 370.20 METAL NOT APPROVED 3) TIGHTEN LOOSE CONDUIT FITTINGS TO A/C 4) ATTACH FIXTURES TO GRID 410-16 |
| 09/15/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0950*/ HAVE REVISED PANEL SCHEDULE APPROVED BY PLAN REVIEW. WAS WATER HEATER ADDED? 2) ADD BLANK COVER OVER CIRCUIT BREAKER OPENING. |
| 09/10/2003 |
ELECTRIC - FINAL |
|
Cancelled |
IVRS - Ri canceled |