Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM03648
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
09/05/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK RESTROOM WALLS, HARD CEILING, OK WATER HEATER CONDUIT, DISCONNECT. | |
09/03/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) PLEASE VERIFY WHO LICENSED L-11 ELECTRICAL CONTRACTOR IS. 2) M/C CABLE TO BE SUPPORTED AS PER 334-10. 3) ALL JUNCTION BOXES TO BE ACCESSABLE. 4) FINISH BOXES IN CEILING. 5) WHERE ARE APPROVED ELECTRICAL DRAWINGS? 6) PLEASE OPEN UP CEILING THAT WAS REINSTALLED AS DISCUSSED. | |
08/27/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) CANCELLED BY JESUS | |
08/08/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) ANSWERED QUESTIONS TO GENERAL CONTRACTOR | |
08/07/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) NEED AN APPROVED AND STAMPED ELECTRICAL SHEET ON SITE 2) HAVE 02036 AND 02061 ADDED TO PERMIT 3) INSTALL TEMP POWER FOR CONSTRUCTION AS PER ATTACHED CITY OF TUCSON PAPER WORK 4) SEE WRITE-UP FOR RECONNECT PERMIT AND T03EL01195 |