Permit: T03CM03648

Parcel: 12108001B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM03648

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
09/05/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK RESTROOM WALLS, HARD CEILING, OK WATER HEATER CONDUIT, DISCONNECT.
09/03/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) PLEASE VERIFY WHO LICENSED L-11 ELECTRICAL CONTRACTOR IS. 2) M/C CABLE TO BE SUPPORTED AS PER 334-10. 3) ALL JUNCTION BOXES TO BE ACCESSABLE. 4) FINISH BOXES IN CEILING. 5) WHERE ARE APPROVED ELECTRICAL DRAWINGS? 6) PLEASE OPEN UP CEILING THAT WAS REINSTALLED AS DISCUSSED.
08/27/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED BY JESUS
08/08/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) ANSWERED QUESTIONS TO GENERAL CONTRACTOR
08/07/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) NEED AN APPROVED AND STAMPED ELECTRICAL SHEET ON SITE 2) HAVE 02036 AND 02061 ADDED TO PERMIT 3) INSTALL TEMP POWER FOR CONSTRUCTION AS PER ATTACHED CITY OF TUCSON PAPER WORK 4) SEE WRITE-UP FOR RECONNECT PERMIT AND T03EL01195