Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T03CM03629

Parcel: 141172730

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/12/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 11/13AM
11/10/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*