Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/19/2004 |
MECHANICAL - FINAL |
|
Approved |
FEES PAID $54.00 |
| 04/15/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ WILL APPROVE JOB WHEN RE-FEE IS PAID. |
| 04/14/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0935*/ NO PERSON ON SITE 9:10 AM. RELIEF LINE DISCHARGE PIPING, OK. REFRIG SENSOR ALARM TEST RESULTS? REFEE DUE. RECALL FOR FINAL. |
| 11/20/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) RELIEF VALVES - INCREASE DISCHARGE LINE PROPORTIONATLY AS ADDITIONAL LINES ARE CONNECTED. 2) HAS REFRIG SENSOR SYSTEM BEEN CHECKED? ACCTUATED? WANT COPY OF TEST RESULTS. 3) PROPER FUSING ON CHILLER AS NECESSARY. |