Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM03617
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2004 | MECHANICAL - FINAL | Approved | FEES PAID $54.00 | |
04/15/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ WILL APPROVE JOB WHEN RE-FEE IS PAID. | |
04/14/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0935*/ NO PERSON ON SITE 9:10 AM. RELIEF LINE DISCHARGE PIPING, OK. REFRIG SENSOR ALARM TEST RESULTS? REFEE DUE. RECALL FOR FINAL. | |
11/20/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) RELIEF VALVES - INCREASE DISCHARGE LINE PROPORTIONATLY AS ADDITIONAL LINES ARE CONNECTED. 2) HAS REFRIG SENSOR SYSTEM BEEN CHECKED? ACCTUATED? WANT COPY OF TEST RESULTS. 3) PROPER FUSING ON CHILLER AS NECESSARY. |