Permit: T03CM03605

Parcel: 124160980


Addresses:

1410 S PARK AV

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
03/29/2004 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*
03/26/2004 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*/ 1) DRYWALL SCREWS NOT ALLOWED TO MOUNT SERVICE PANEL 2) 1/4" SCREWS LONG ENOUGH TO PENETRATE STRUCTURE A MINIMUM OF 7/8" ARE REQUIRED IN ALL MOUNTING HOLES 3) HAVE COVERS REMOVED FOR INSPECTION
03/23/2004 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*/ 1) ELECTRIC PANEL DOES NOT APPEAR TO BE PROPERLY INSTALLED PROVIDE G. E. INSTALLATION INSTRUCTIONS
03/22/2004 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*/ 1) SEE PREVIOUS INSP
03/18/2004 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*/ 1) RISER FACING WRONG DIRECTION 2) SUPPORT SERVICE CAN 3) TRENCH NOT COMPLETE