Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/04/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/03/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) REMOVE STAPLES BEHIND HOME RUNS AND BEHIND ABS INSIDE GARAGE PEDESTRIAN DOOR 2) BANG PLATE PEX AT TPR DRAIN AND AT 3" ABS ABOVE LAUNDRY BOX AND WIRES AT NORTH DINING WALL AND AT MASTER TUB 3) 3" ABS IN GARAGE DOOR CHASE ? 4) NEED WATER PRESSURE AND DWV 5) SHIM HEADER IN NORTH ENTRY ROOM WALL AND FIREBLOCK EAST WALL CHASE AND KITCHEN PASS THROUGH CHASE 6) REPLACE HVAC COPPER AT WALL EXTERIOR EXCIT 7) HALL BATH LAV PEX OUT OF WALL 8) REPAIR FIREBLOCK AT MASTER TUB 9) NEED SIMPSON LSSU 210 AT STRINGER TOPS PER D-7-4 10) RE-INSTALL CEILING LIGHT BOX IN MASTER TOILET |