Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/27/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NEED POSITIVE CONNECTION ALL BEAMS RAFTERS GAZEBO 2) GROUND ALL METAL ELECTRIC BOXES 3) NO GAUGE-NO PRESSURE 4) CANNOT LOCATE REVISE MECH-DRAWINGS. BLOCK 3 SIDES MECH VENTS 5) STOPPED INSPECTION. INCOMPLETE |
|
| 05/11/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) INSTALL HORIZONTAL FIRESTOPS MAXIMUM 10' OF RUN (STUDS) 2) PORCH RAFTERS 16" ON CENTER SPACING ON PLAN 3) NEED APPROVED TRUSS DRAWINGS 4) PLAN SHOWES TJI'S HUNG OFF LEDGE 5) GROUND NEW SUB-PANEL 6) NAIL PROTECT ELECTRIC (HOLES WITHIN 1 1/4" OF STUD FACE) 7) MECH NOT TO PLAN 8) GAS TEST REQUIRED 9) STOPPED INSPECTION 10) COMPLETE ALL TRADES AND RECALL |