Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2004 |
ELECTRIC - TEMPORARY SERVICE |
|
Approved |
IVRS - Inspection 0000* |
| 03/26/2004 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999*/ 1) DRYWALL SCREWS NOT ALLOWED TO MOUNT SERVICE PANEL 2) 1/4" SCREWS LONG ENOUGH TO PENETRATE STRUCTURE A MINIMUM OF 7/8" ARE REQUIRED IN ALL MOUNTING HOLES 3) HAVE COVERS REMOVED FOR INSPECTION |
| 03/23/2004 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999*/ 1) ELECTRIC PANEL DOES NOT APPEAR TO BE PROPERLY INSTALLED PROVIDE G. E. INSTALLATION INSTRUCTIONS |
| 03/22/2004 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999*/ 1) SEE PREVIOUS INSP |
| 03/18/2004 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999*/ 1) REMOVE STUCCO AT PANEL SUPPORTS FOR SOLID ATTACHEMENT TO WALL |