Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
Permit Number - T03CM03551
Inspection Description - PLUMBING - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
10/19/2004 | PLUMBING - FINAL | Approved | ||
10/05/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)NO APPROVED PLAN ON SITE. NOT INSTALLED PER PLAN THAT IS ON SITE (RELOCATION OF FLOOR SINKS) 2)COUNTER SINK TAPPED CLEAN OUT PLUGS HAVE NOT BEEN INSTALLED 3)NO EXPANSION TANK ON WATER HEATER |
|
08/13/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :PLUMBING IN RESTROOMS NOT INSTALLED PER DETAILS P-1 DETAIL ONE SEE NOTE #1 FROM 1/15/04 EACH METER SUPPLIED APPLIANCE TO HAVE ITS OWN BACKFLOW PROTECTION WOOD SCREWS DRILLED INTO RAISED SQ. HEAD TEST PLUG NOT APPROVED ALL CLEANOUTS NEED TO BE COUNTER SUNCK TAPPED PLUGS |
|
01/15/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) WHAT ABOUT FLOOR C.O. UNDER CABINET. 2) CONTRACTOR REQUESTS TEMP C OF O BECAUSE A SS TOP WITH SINK IS BACK ORDERED. OK FOR TEMP C OF O SUBJECT TO OTHER INSPECTORS AND STEVE LONG. | |
01/14/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
01/13/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ MAKE ALL CONNECTIONS. HOOK UP ALL EQUIPMENT. |