Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/24/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/23/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CLIPS AT GARAGE NOT REPLACED. - SHEER WALL CONNECTION TO TRUSS. 2) ELECTRICAL AT PONY WALL NOT MADE UP. 3) OK TO ROCK. LEAVE THOSE AREAS OPEN FOR INSPECTION. |
| 10/22/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CLIPS AT GARAGE TO FLOOR TRUSS CONNECTION NOT NAILED PER MANUFACTURER INSTRUCTIONS. 2) ON HORIZONTAL OR VERTICAL RUNS FOR ELECTRICAL AND PLUMBING THE 1 1/4" AND 1 1/2" CLEARANCE STILL APPLIES 3) MOVE ELECTRIC FROM GANG NAILS IN FLOOR 4) FUR OUT NOT PER CODE AT POWDER ROOM 5) NAIL PROTECT PLUMBING AT LAUNDRY ROOM 6) SECURE OUTLET AT HALL WAY AND HALL BATH 7) FIRE BLOCK MISSING AT STAIR STRINGER 8) WATER LINES OK |
| 10/21/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* 1) SEE PREVIOUS INSPECTION 2) REFEE IMPOSED, PAY PRIOR TO NEXT INSPECTION |
| 10/20/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) VENT FOR WATER HEATER NOT CONNECTED 2) SECURE ELECTRIC BOX AT 2ND FLOOR BATH 3) FILL TUBS FOR DWV TEST |
| 10/16/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NO TEST ON DWV'S 2) MECHANICAL DUCT HANGING AT DINING ROOM AREA 3) FIRE BLOCK MISSING AT STRINGER 4) EXHAUST FAN IN POWDER ROOM NOT CONNECTED 5) STOPPED INSPECTION RECALL WHEN READY |