Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/22/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : GAS METER AND PIPING IN VIOLATION OF 110-26 INSUFFICIENT CLEARANCE IN FRONT OF SERVICE. GAS METER, PIPING AND ALL ASSSOCIATED. |
|
| 09/17/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PVC CONDUIT TO BE 18' AS PER 300.5 2) AN APPROVED EXTENDER RING IS NEEDED AT COMBUSTIBLES 3) MAINTAIN WORKING CLEARANCES IN FRONT OF A/C DISCONNECT 110.26 |