Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM03532

Parcel: 117080740


Addresses:

215 E 19TH ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T03CM03532

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/30/2004 BUILDING - FINAL Approved IVRS - Inspection 0000*
03/23/2004 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) INSTALL CONCRETE STOOP OUTSIDE DOOR 2) SECURE LIQUID-TITE TO WALL 3) NEED LADDER TO ACCESS ROOF 4) INSTALL PROPER CONNECTIONS LIQUID-TITE CONDUIT 5) 20 AMP CIRCUITS REQUIRE #12 WIRE 6) CUT SEWER CLEANOUTS TO GRADE 7) WHAT IS 1/2" COPPER STUBBED OUTSIDE FOR ? 8) ELECTRIC BASE BOARD HEATER NOT INSTALLED PER PLAN 9) INSTALL SMOKE DETECTORS ALL BEDROOMS AND HALL WAY AND NEW DINING ROOM 10) NEED EXHAUST FAN IN EXISTING BATH 11) NEED INSIDE TO INSPECT J-BOX IN ATTIC 12) LABEL CIRCUITS MAIN PANEL 13) WHAT ARE ALL UNUSED BREAKERS FOR IN MAIN PANEL ? 14) COMPLETE GRADING TO SLOPE AWAY FROM HOUSE 15) STOPPED INSPECTION