Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T03CM03525
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2004 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
03/31/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ HEATING - HOT WTR COIL IN AIR HANDLER CL - DIRECT EXPANSION EVAP. NO COMB/RELIEF DUCTS NECESSARY. | |
03/24/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) KITCHEN HOOD EXHAUST DUCT. PROVIDE MANUFACTURERS INSTALLATION INTRUCTIONS TO SHOW EXHAUST DUCT 2"X10" IS SUFFICENT FOR HOOD BEING USED. 2) COMBUSTION/RELIEF AIR DUCTS INTO FURNACE AND WTR HTR LOCATION. HOW WILL THIS AIR BE ISOLATED FROM INDOOR LIVING AREA?? COMB/RELIEF AIR VENTS (ON TOP SIDE) NEED TO BE LOWERED. 3) WTR HTR VENT TERMINATION - IMC SEC. 804.3.4. SEE #1, 2, 3, TERMINATES TOO CLOSE TO A WINDOW. |