Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/01/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) CONTRACTOR TO SUPPORT OVERHEAD HORIZONTAL ABS AS REQUIRED. 2) CORRECTIONS MADE OK. 3) OK TO COVER ALL AREAS. |
| 03/31/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/PLEASE READ AND COMPLY WITH ALL CORRECTIONS. SEE NOTE#3 FROM 3/26/04 |
| 03/26/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NOT INSTALLED PER PLAN - SEE PLBG ISOMETRIC AT P-1. 2) HOT AND COLD PEX MAY NOT BE BUNDLED TOGETHER (HEAT TRANSFER). 3) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE THRU WYE BRANCH OR EQUIVELENT SWEEP. |
| 03/24/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST OK 2) NO TEST ON DWV PIPING |