Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM03525

Parcel: 117101540


Addresses:

421 N COURT AV


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T03CM03525

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2004 ELECTRIC - UFER Approved IVRS - Inspection 0000*
01/08/2004 ELECTRIC - UFER Denied IVRS - Inspection 0999*/ 1) NO INFO ON REVISED PLANS AS TO SIZE OF SERVICE, SIZE OF GROUND OR # OF METERS-NEED ONE LINE DIAGRAM OF SERVICE
10/16/2003 ELECTRIC - UFER Partial Approval IVRS - Inspection 0000*/ GET A REVISED PLAN FOR UFER. THERE IS A 1/10 COPPER TIED TO REBAR - OK IF REVISION APPROVED.
10/13/2003 ELECTRIC - UFER Partial Approval IVRS - Inspection 0000*/ 1) OK #4 TO REBAR-IF INSTALLING LARGER THAN 100 AMP METER BASE AS PER PLANS, WEE NEED A REVISED PLAN FOR METER PACKS AND A REVISION FOR UFER IF NECESSARY