Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/05/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/29/2003 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ WORK IS INCOMPLETE. 1) DO NOT BUNDLE MC CABLES. 2) SUPPORTS REQUIRED WITHIN 12" OF BOXES AND EVERY 6' THERE AFTER. RECALL WHEN REST OF ROUGH IN IS COMPLETE. |
| 08/26/2003 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |