Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM03518
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) APPROVED FOR TEMP C OF O | |
08/14/2003 | ELECTRIC - FINAL | Denied | 1) FRONT ENTRANCE - RE INSTALL FA DEVICE ( OPEN WIRING OUT OF WALL. 2) BATHROOMS (TWO) ELECTRICAL BOXES OPEN (OPEN WIRING OUT OF WALL) AT NEW ADA RESTROOMS TEACHERS LOUNGE. 3) FIRE ALARM STATION AND J-BOX IN CAFETERIA AND MULTI-PURPOSE ROOM WIRING UNFINISHED AND EXPOSED. ALSO EXPOSED WIRING AT CEILING ON WEST WALL. 4) HALLWAY WHERE PNLS C-1, C-2, L-1, LOCATED, EXPOSED WIRING OUT OF WALL WEST SIDE AND FIRE ALARM BOX EAST SIDE. 5) EXPOSED WIRING NO DEAD-END ON RECEPTACLE CLASS ROOM #1. 6) LIGHTS IN CLASSROOM #2 NOT WORKING. 7) EXPOSED ROMEX WIRE HANGING DOWN WALL CLASSROOM #3. 8) PNL C-3 CLOSE OFF OPEN BREAKER SLOT. 9) FIRE SPRINKLER ALARM SENOID DISCONNECTED, CLASSROOM #9 CLOSET. | |
08/12/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*/ 1) LOCKED, PLEASE RECALL | |
07/22/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ PLEASE HAVE ALL ROOMS UNLOCKED. NEED TO INSPECT SERVICE EQUIPMENT. PROVIDE ELECTRICAL ONE LINE DIAGRAM. NOTE: DEPENDING ON OUTCOME OF SERVICE INSP. (AND BLDG INSP.), THIS WILL ENABLE THE POWER TO BE TURNED ON BUT NOT A C OF O BECAUSE OF ALARM SYSTEM AND OPEN WIRES. | |
07/21/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ UNRESOLVED INSPECTION FROM ACCT. # T98CM04090. WILL NEED TO CONSULT WITH RAY MAJUTA. |