Permit: T03CM03504

Parcel: 110055580

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM03504

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK FINAL
07/21/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) FINISH #2 OF PREVIOUS INSPECTION
04/05/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ RECEIVED COPY OF APPROVED SERVICE PLAN REVISIONS./ 1) RE-INSTALL ARC SHIELD IN MAIN DISCONNECT. 2) EM LIGHTING NOT WORKING. 3) WALL LIGHTS ARE TEMP AS PER STEVE OF WILLIAMSON. 4) FINISH ALARM CIRCUIT.
04/02/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ CANCELLED BY OFFICE.
03/26/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
03/26/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) CALLED MARK NO TEP POWER AT THIS TIME-INSPECTION REQUIRES POWER
03/25/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) WE HAVE OVER FILL FOR CONDUCTOR AT JUNCTION BOXES 2) CHECK FOR ? OF CONDUCTOR PER 310.15 3) TIGHTEN LOOSE FITTINGS 4) NEED TO VERIFY WORKING EM LIGHTING AFTER POWER IS ON
03/23/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK TEMP POWER FOR TEST SUBJECT TO OTHER INSPECTION AND STEVE LONG
03/22/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) FINISH INSTALLATION OF SERVICE AND CLOSE-UP JUNCTION BOXES