Permit: T03CM03500

Parcel: 12511199B


Addresses:

780 N RICHEY BL #03

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/23/2004 FRAMING Approved IVRS - Inspection :*
1) OK TO INSULATE
12/22/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIRESTOP ALL DROPPED CEILINGS
2) REPLACE ACCESSIBLE BOLTS AT HD5A HOLDOWNS
3) FIRESTOP AROUND KNOTCHED PLUMBING 2ND FLOOR AND 1ST FLOOR
12/20/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED CITY OF TUCSON STAMPED APPROVAL FOR SINGLE STUD/TRIMMER METHOD
2) OVER KNOTCHED BEAM AT LAUNDRY HEADER
3) SEAL GAPS FIRST FLOOR BATH SOLE PLATES
4) FIREBLOCK STAIRWELL
5) LADDER BACK UPSTAIRS WALLS
6) FIRE BLOCK ABOVE MASTER BEDOOM SLIDING DOOR
7) FIREBLOCK ABOVE UP STAIRS TUB, NORTH WALL AND FIREPLACE
12/15/2004 FRAMING Denied 1) MISSING NAILS IN HANGERS ABOVE GARAGE ENTRY DOOR AT TOP OF SHEARWALL TJI'S
2) NAIL ALL TJI HANGERS PROPERLY/MISSING NAILS
3) COMPLETE LATH WEST WALL
4) CAULK ALL PENETRATIONS
5) NAIL PROTECT ROMEX THROUGHOUT HOME
6) NO WATER TEST IN DWV SYSTEM
7) PROPERLY CONNECT FLEX LINE IN LAUNDRY ROOM
8) STRAP LEDGER IN BATHROOM
9) FIRESTOP FIRPLACE FLUE
12/07/2004 FRAMING Not ready for Inspection IVRS - Inspection :*/ 1) CONSULTATION ONLY
2) CALL FOR NAIL AND CLIP INSPECTION
05/20/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) 2'-8" BRACE WALLS ON 1ST FLOOR ARE NOT PER CODE 2) 2ND FLOOR BAY WINDOW < 3' FROM DUPLEX TO WEST 3) TJI'S CANTILEVERED 46" WITH POINT LOADS ON CANTILEVERED 4) MANY TRIMMERS ARE NOT TOUCHING HEADERS 5) PRIOR INSPECTION SHEET MUST BE LEFT ON SITE 6) RENAIL SHEAR AT N.E. CORNER 2ND FLOOR 7) 2ND FLOOR WALL ACROSS FROM DUPLEX WINDOW MUST BE 1 HR. 8) INSTALL ELECTRIC PANEL 9) INSTALL STUCCO MECH PRIOR TO RECALL
05/05/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SINCE THE 2/25/04 INSPECTION, THERE IS NO EVIDENCE THAT AN ATTEMPT HAS BEEN MADE TO CORRECT THE PROBLEMS. A RE-INSPECTION FEE WILL BE ADDED
04/02/2004 FRAMING Denied IVRS - Inspection 0950*/ 1) COMMENTS FROM LAST INSPECTION HAVE NOT BEEN ADDRESSED
03/31/2004 FRAMING Denied IVRS - Inspection 0925*/ 1) SECOND FLOOR NOT BUILT PER PLAN. SECOND FLOOR IS ONLY 3 FEET FROM DUPLEX ON WEST 2) HOLDOWNS MUST BE CONNECTED FALL LENGTH DOUBLE STUDS NOT BLOCKS 3) NO APPROVED PLANS ON SITE 4) NO APPROVED PLAN ON SITE