Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/03/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 08/18/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) HAVE PLUMBER COMPLETE PUNCH LIST BEFORE CALLING FINAL. SOME OF THE INCOMPLETE ITEMS INCLUDE: LOOSE WATER CLOSET AT SINGLE TOILET ROOM 2) CLEARANCES AT WATER CLOSETS. REQUIRED 15" FROM CENTER TO SIDE WALL OF OBSTRUCTION 3) CLEANOUTS THAT UTILIZE A CP COVER REQUIRE COUNTER SUNK TAPPED PLUGS W/MACHINE SCREW |
| 07/23/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |