Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 08/18/2004 |
PLUMBING - PROGRESS |
|
Approved |
IVRS - Inspection :* |
| 07/08/2004 |
PLUMBING - PROGRESS |
|
Partial Approval |
IVRS - Inspection :*/ 1) CONTRACTOR WISHES TO COVER SINGLE BATH 2) CLOSET FLANGE OK 3) LOOPED COPPER OK 4) ABS INSTALLED OK-OK TO COVER SUBJECT TO WATER TEST |
| 06/25/2004 |
PLUMBING - PROGRESS |
|
Partial Approval |
IVRS - Inspection :*/ 1) BAR AREA ONLY OK TO COVER. A) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A WYE OR EQUIVELENT (SWEEP). B) HORIZONTAL VENTING BELOW FLOOD RIM TO BE SWEEPS. C) PERM CAP REQUIRED ON UNUSUAL RISER. D) SUPPORT OVERHEAD VENT - SUPPORTS REQUIRED AT END OF BRANCHES, CHANGE OF DIRECTION, CHANGE OF ELEVATION. |