Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T03CM03499
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/04/2004 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :*/ 1) OK TO COVER ALL AREAS 2) WATER TEST OK 3) CORRECTIONS MADE OK | |
07/22/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :TEST OK ON WATER AND VENTS FOR UL NOT READY ON LAV'S SEE PLAN WATER PROVIDED REVISED PLAN AT U.L. UNDER SIZED TO PLAN |
|
07/20/2004 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SHALL PROVIDE WATER TEST TO TOP OF VENT THRU ROOF |
|
07/19/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :*/ 1) WASTER AND VENT SYSTEM IN WOMEN'S RESTROOM IS OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) OK TO DRY WALL WOMENS RESTROOM ONLY | |
07/13/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/ 1) WOMEN'S BATHROOM ABS UNDERSLAB OK TO COVER CAP OFF ALL OPEN PIPES | |
07/09/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :*/ 1) NO TEST ON ABS 2) VERTICAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP 3) INSPECTION STOPPED | |
05/26/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/ 1) BAR AND SINGLE BATHROOM UNDERGROUND OK TO COVER SUBJECT TO REDLINE 'AS BUILTS' 2) OK TO COVER THESE AREAS. |