Permit: T03CM03475

Parcel: 12710229A


Addresses:

603 N WILMOT RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM03475

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2004 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
09/28/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*1)PLEASE VERIFY CRESTRON? SYSTEM FOR USE IN A PLENIUM?
06/18/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) TRANSFORMER NEEDS GROUNDING SYSTEM AND DISCONNECT TO HAVE CLEARANCE AND LABEL. 2) PLEASE PROVIDE FOR FAN COIL REVISION. 3) FINISH VDV AS DISCUSSED. - 0K ROOMS 132, 134, 151, 153-155, 138, 139, 141, 148, 149.
06/08/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ OK ENTRY LIGHTING LOBBY 101.
05/28/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) CORRECTLY SUPPORT VDV BOXES ABOVE CEILING - NOT ON A CHAIN SWING. 2) VDV CABLES LAYING ON GRID. OK 215-223, 225-239. PARTIAL 240.
05/21/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) OK ROOM # 001-003, 006-008, 010, 015, 014, 125 AND 106
05/14/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) BOXES IN CEILING TO BE SUPPORTED. 2) FINISH BOX MAKE-UP. * STILL WAITING ON LETTER FOR FIXTURE SUPPORTS. OK ABOVE CEILING RM 104, 105, 107, 112, 119, EXCEPT AS NOTED.
05/13/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) PLUGS ARE ALLOWED ABOVE CEILING - NO CORDS ALLOWED 400-7, 400-8. RECEIVED LETTER FOR CONDUCTOR SIZES. OK ABOVE CEILING ROOMS 126-129, 144-147, 157 A&B. OK PANELS ILA, ILAA, ILD, ILDD, ILE, ILB.
04/28/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) PARTIAL FOR FOLLOWING ROOMS 2ND FLOOR ? TO ? OK TO TILE 2) OK 4" CONDUITS FROM TEP TRANS TO SW GEAR SEALED OK ON 600 ? TO 500 ? POLARIS SPLICE, LETTER FORTH COMING
04/23/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :
See detailed listing on site.| 999*/ 1) OK DATA ROOM DAC 1-4 AND UPS 1-4 2) OK UNDER FLOOR 3) OK PANELS 1LC, 1LCC, 1HA 4) OK NORTH WEST STAIR WELL 5) CONTRACTOR TO MAINTAIN LOCK OUT TAG OUT AS SUBMITTED FOR SAFETY
04/16/2004 ELECTRIC - ABOVE CEILING Partial Approval ALL ABOVE CEILING FROM K THRU D 1ST FLOOR, OK TO COVER.
04/15/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ DISCUSSED CORD CONNECTORS UNDER 400-7 AND 400-8 WITH CONTRACTOR.
04/14/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) OK HARD CEILING #280 AND 276 2) OK ABOVE CEILING 159, 165-169 (COL J-K) 2ND FLOOR: 1) PLEASE PROVIDE MANUFACTURER INSTALLATION INSTRUCTIONS 2) FIXTURE TO BE ATTACHED TO GRID 410.16 3) SUPPORT CONDUIT WITHIN 3' OF BOXES 4) CORDS NOT ALLOWED ABOVE SEALING 400.8. INSTALL PROTECTIONS AS PER MANUFACTURERS INSTALLATION INST. 1ST FLOOR: 1) SUPPORT SECURITY CABLES OFF GRID
04/07/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) OK WALLS AND HARD CEILING ROOM 101 2) OK SOFFITS ROOM 228
04/05/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ OK CANS 2ND FLOOR LOBBY AND HIGH CEILING.
04/02/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ OK ROOMS 132, 149, 170.
03/16/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ ROOM #280: 1) SUPPORT CONDUIT AS PER CODES 3' AND 10' 2) TIGHTEN LOOSE FITTINGS 3) JUNCTION BOXES TO BE ACCESSIBLE
03/12/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ OK CANS AND SPECIALTY CANS ROOM 143.
01/15/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) OK CANS IN OUTSIDE ALL SOFFITS