Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T03CM03475
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
09/28/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*1)PLEASE VERIFY CRESTRON? SYSTEM FOR USE IN A PLENIUM? | |
06/18/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) TRANSFORMER NEEDS GROUNDING SYSTEM AND DISCONNECT TO HAVE CLEARANCE AND LABEL. 2) PLEASE PROVIDE FOR FAN COIL REVISION. 3) FINISH VDV AS DISCUSSED. - 0K ROOMS 132, 134, 151, 153-155, 138, 139, 141, 148, 149. | |
06/08/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ OK ENTRY LIGHTING LOBBY 101. | |
05/28/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) CORRECTLY SUPPORT VDV BOXES ABOVE CEILING - NOT ON A CHAIN SWING. 2) VDV CABLES LAYING ON GRID. OK 215-223, 225-239. PARTIAL 240. | |
05/21/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) OK ROOM # 001-003, 006-008, 010, 015, 014, 125 AND 106 | |
05/14/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) BOXES IN CEILING TO BE SUPPORTED. 2) FINISH BOX MAKE-UP. * STILL WAITING ON LETTER FOR FIXTURE SUPPORTS. OK ABOVE CEILING RM 104, 105, 107, 112, 119, EXCEPT AS NOTED. | |
05/13/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) PLUGS ARE ALLOWED ABOVE CEILING - NO CORDS ALLOWED 400-7, 400-8. RECEIVED LETTER FOR CONDUCTOR SIZES. OK ABOVE CEILING ROOMS 126-129, 144-147, 157 A&B. OK PANELS ILA, ILAA, ILD, ILDD, ILE, ILB. | |
04/28/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) PARTIAL FOR FOLLOWING ROOMS 2ND FLOOR ? TO ? OK TO TILE 2) OK 4" CONDUITS FROM TEP TRANS TO SW GEAR SEALED OK ON 600 ? TO 500 ? POLARIS SPLICE, LETTER FORTH COMING | |
04/23/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection : See detailed listing on site.| 999*/ 1) OK DATA ROOM DAC 1-4 AND UPS 1-4 2) OK UNDER FLOOR 3) OK PANELS 1LC, 1LCC, 1HA 4) OK NORTH WEST STAIR WELL 5) CONTRACTOR TO MAINTAIN LOCK OUT TAG OUT AS SUBMITTED FOR SAFETY |
|
04/16/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | ALL ABOVE CEILING FROM K THRU D 1ST FLOOR, OK TO COVER. | |
04/15/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ DISCUSSED CORD CONNECTORS UNDER 400-7 AND 400-8 WITH CONTRACTOR. | |
04/14/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) OK HARD CEILING #280 AND 276 2) OK ABOVE CEILING 159, 165-169 (COL J-K) 2ND FLOOR: 1) PLEASE PROVIDE MANUFACTURER INSTALLATION INSTRUCTIONS 2) FIXTURE TO BE ATTACHED TO GRID 410.16 3) SUPPORT CONDUIT WITHIN 3' OF BOXES 4) CORDS NOT ALLOWED ABOVE SEALING 400.8. INSTALL PROTECTIONS AS PER MANUFACTURERS INSTALLATION INST. 1ST FLOOR: 1) SUPPORT SECURITY CABLES OFF GRID | |
04/07/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) OK WALLS AND HARD CEILING ROOM 101 2) OK SOFFITS ROOM 228 | |
04/05/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ OK CANS 2ND FLOOR LOBBY AND HIGH CEILING. | |
04/02/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ OK ROOMS 132, 149, 170. | |
03/16/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ ROOM #280: 1) SUPPORT CONDUIT AS PER CODES 3' AND 10' 2) TIGHTEN LOOSE FITTINGS 3) JUNCTION BOXES TO BE ACCESSIBLE | |
03/12/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ OK CANS AND SPECIALTY CANS ROOM 143. | |
01/15/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) OK CANS IN OUTSIDE ALL SOFFITS |