Permit: T03CM03474

Parcel: 123060950


Addresses:

2150 E ADAMS ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
01/23/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
01/22/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED
01/21/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) SWEEP FITTING REQUIRED ON VERTICAL TO HORIZONTAL DRAIN 2) MAXIMUM DISTANCE FROM 2" TRAP TO VENT IS 60" 3) 10' WATER TEST REQUIRED 4) CONNECT ALL DRAINAGE TO BE INCLUDED IN TEST