Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/23/2004 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 01/22/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCELLED |
| 01/21/2004 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) SWEEP FITTING REQUIRED ON VERTICAL TO HORIZONTAL DRAIN 2) MAXIMUM DISTANCE FROM 2" TRAP TO VENT IS 60" 3) 10' WATER TEST REQUIRED 4) CONNECT ALL DRAINAGE TO BE INCLUDED IN TEST |