Permit: T03CM03436

Parcel: 130040930

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/26/2007 BUILDING - FINAL Approved IVRS - Inspection :*
07/24/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GFI OUTLET REQUIRED IN GARAGE
2) 3 SCREWS REQUIRED AT W/H VENT AT DIVERTER
3) EXPOSE WATER LINE TRACER WIRE BOTH ENDS
4) BOND GAS LINE
07/10/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE ARC FAULT ON BEDROOM CIRCUITS
2) REMOVE DEAD RAT AT MAIN PANEL
3) KITCHEN REQUIRES TWO 20 AMP CIRCUITS
4) PLUG UNUSED OPENINGS AT MAIN PANEL
5) PROVIDE ANTI-SIPHON OF HOSE BIBS AT EXTERIOR
6) NEED GFCI PROTECTION ON ALL AT GRADE RECEPTACLES GARAGE
7) SEDIMENT TRAP AT WATER HEATER ON WRONG SIDE OF SHUT OFF VALVE
8) PRIOR INSPECTIONS WERE NOT APPROVED ?
9) NEED LADDER TO ACCESS ROOF CHECK A/C